There are two main approaches. Aquifer thermal energy storage (ATES) uses natural water-bearing layers underground, where heat and cold are stored in groundwater and recovered through wells. Water-gravel thermal energy storage (WGTES), in contrast, uses built, usually insulated basins filled with gravel and water. Both technologies share a common challenge: their performance depends on how they interact with the surrounding subsurface. Two new studies look at this from different angles.
Water-gravel storage: Making the most of existing basins
Within the EU project INTERSTORES, one key idea is to give existing structures a second life instead of building new storage from concrete, for example the former firewater basins at the incampus in Ingolstadt, Germany. This saves material and CO₂. However, such structures often consist of several adjacent basins. Is that a drawback? Our new study uses coupled numerical simulations to find this out, and the answer is: quite the opposite. When the basins are charged one after another in a smart sequence, more heat can be used in winter than with a single large basin. The subdivided storage in Ingolstadt is scheduled to start operation later this year under scientific monitoring.
→ Learn more about INTERSTORES

Reusing legacy infrastructure as seasonal thermal energy storage: Our study tests different charging strategies: serial, hybrid or parallel. (a): Large WGTES under construction at incampus in Ingolstadt. (b): Schematic cross section of the incampus WGTES under transformation.
Aquifer storage: How the subsurface shapes performance
ATES can store and recover heat between seasons and is a promising option for reducing heating and cooling demand in buildings. In aquifers, groundwater flow is affected by geological heterogeneity, while water density and viscosity can also change with temperature. We used 3D stochastic numerical models to investigate how aquifer heterogeneity, injection temperature, and temperature-dependent fluid properties affect the performance of a low-temperature doublet ATES (LT-ATES) system. The results show a clear difference between the warm and cold wells. The warm well remained relatively stable across the investigated temperature range, while the cold well was much more sensitive to subsurface structure and increasing warm-well injection temperature. In less favorable geological conditions, cold-well performance decreased strongly as injection temperature increased, showing that average thermal recovery alone may hide important performance risks.
Temperature-dependent density had only a small influence under the studied conditions, while temperature-dependent viscosity had a stronger effect, especially on the cold well. Stronger groundwater flow reduced thermal recovery, while larger well spacing helped reduce thermal interference.
Overall, the results show that both average performance and lower-performing cases should be considered when assessing ATES reliability in heterogeneous aquifers.

3D model setup of the ATES doublet and examples of heterogeneous aquifer structures used in the simulations. The red and blue dots mark the warm and cold wells, respectively.
Outlook
Together, the two studies show that the success of seasonal heat storage depends not only on the technology itself, but also on how it is operated and how it interacts with its surroundings. Whether in natural aquifers or in reused concrete basins, the subsurface and the operating strategy strongly influence how much heat can be recovered in winter. Computer models help identify opportunities and risks before a system is built. Field data from real sites are the next step towards reliable seasonal heat storage in everyday use.